Кількість
|
Вартість
|
||
|
CHARX-PROTECT-11-22KW is a surge protection set optimized for use with charging stations. The cable gland specifically selected for this purpose enables the insertion of commercially available H07RN-F cables of 2.5 mm2 to 6 mm2, without restricting the IP protection class.
IEC test classification | II |
EN type | T2 |
Product type | Surge arrester |
Surge protection fault message | Optical, remote indicator contact |
Nominal frequency fN | 50 Hz (60 Hz) |
Indicator/remote signaling | |
Connection name | Remote fault indicator contact |
Switching function | Changeover contact |
Connection method | Push-in connection |
Conductor cross section solid | 0.5 mm² ... 10 mm² |
Conductor cross section AWG | 20 ... 8 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.5 mm² ... 6 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.5 mm² ... 10 mm² |
Remote fault indicator contact | |
Connection method | Push-in connection |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 30 ... 12 |
Width | 130 mm |
Height | 180 mm |
Depth | 111 mm |
Color | transparent |
light grey RAL 7035 | |
Housing material | Polycarbonate |
Nominal voltage UN | 240/415 V AC (TN-S) |
240/415 V AC (TT) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous operating voltage UC (L-N) | 275 V AC |
Maximum continuous operating voltage UC (N-PE) | 260 V AC |
Residual current IPE | ≤ 5 µA |
Nominal discharge current In (8/20) µs | 20 kA |
Maximum discharge current Imax (8/20) µs | 40 kA |
Follow current interrupt rating Ifi (N-PE) | 100 A |
Short-circuit current rating ISCCR | 25 kA |
Voltage protection level Up (L-N) | ≤ 1.35 kV |
Voltage protection level Up (N-PE) | ≤ 1.5 kV |
Max. backup fuse with V-type through wiring | 32 A (gG - 6 mm²) |
35 A (gG - 10 mm²) | |
40 A (MCB C - 10 mm²) |
Ambient conditions | |
Degree of protection | IP65 |
Ambient temperature (operation) | -20 °C ... 40 °C |
Ambient temperature (storage/transport) | -20 °C ... 40 °C |
Permissible humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Standards/specifications | IEC 61643-11 |
Standards/specifications | EN 61643-11 |