Quantity
|
Out of stock
|
||
|
Product type | Single relay |
Set comprises | 2903315 RIF-2-RPT-LDP-24DC/2X21 |
2903326 RIF-2-RSC-LDP-24DC/2X21 | |
Operating mode | 100% operating factor |
Mechanical service life | approx. 2x 107 cycles |
Insulation characteristics | |
Insulation | Basic insulation |
Insulation characteristics | |
Insulation | Basic insulation |
Overvoltage category | III |
Pollution degree | 3 (Rated voltage of 230 V) |
2 (Rated voltage of 400 V) |
Service life electrical | see diagram |
Maximum power dissipation for nominal condition | 1.01 W |
Test voltage (Winding/contact) | 2.5 kVrms (50 Hz, 1 min., winding/contact) |
Test voltage (Contact/contact) | 2.5 kVrms (50 Hz, 1 min., contact/contact) |
Test voltage (Changeover contact/changeover contact) | 2.5 kVrms (50 Hz, 1 min., changeover contact/changeover contact) |
Rated insulation voltage | 250 V AC |
Rated surge voltage | 4 kV |
Coil side | |
Nominal input voltage UN | 24 V DC |
Input voltage range | 18.7 V DC ... 46.8 V DC |
Input voltage range in reference to UN | see diagram |
Drive and function | monostable |
Drive (polarity) | polarized |
Typical input current at UN | 42 mA |
Typical response time | 13 ms |
Typical release time | 14 ms |
Protective circuit | Freewheeling diode |
Status display | Yellow LED |
Switching | |
Contact type | 2 changeover contacts |
Type of switch contact | Single contact |
Contact material | AgNi |
Maximum switching voltage | 250 V AC/DC |
Minimum switching voltage | 5 V (At 24 mA) |
Limiting continuous current | 12 A |
Maximum inrush current | 30 A (20 ms, N/O contacts) |
Min. switching current | 5 mA (at 24 V) |
Interrupting rating (ohmic load) max. | 288 W (at 24 V DC) |
124 W (at 48 V DC) | |
108 W (at 60 V DC) | |
52 W (at 110 V DC) | |
48 W (at 220 V DC) | |
3000 VA (for 250 V AC) | |
Switching capacity min. | 0.12 W |
Motor load according to UL 508 | 1/2 HP, 240 V AC |
Connection method | Plug-in connection |
Width | 21.2 mm |
Height | 27.5 mm |
Depth | 35.6 mm |
Ambient conditions | |
Degree of protection | RT I |
Ambient temperature (operation) | -40 °C ... 70 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Corrosive gas test | |
Identification | ISA-S71.04. G3 Harsh Group |
EN 60068-2-60 |
Standards/regulations | IEC 60664 |
IEC 61810 |
Mounting position | any |