Quantity
|
Out of stock
|
||
|
Product type | Bolt connection terminal block |
Pitch | 18 mm |
Number of connections | 1 |
Number of rows | 1 |
Potentials | 1 |
Insulation characteristics | |
Overvoltage category | III |
Degree of pollution | 3 |
Rated surge voltage | 8 kV |
Maximum power dissipation for nominal condition | 4.06 W |
Number of connections per level | 1 |
Nominal cross section | 35 mm² |
Stripping length | The stripping length depends on the specification provided by the cable lug manufacturer. |
Connection in acc. with standard | IEC 60947-7-1 |
Nominal current | 125 A |
Maximum load current | 125 A (with 35 mm² conductor cross section) |
Nominal voltage | 1000 V |
Nominal cross section | 35 mm² |
Cable lug connection DIN 46234:1980-03 | |
Connection in acc. with standard | DIN 46234:1980-03 |
Cross section | 2.5 mm² ... 35 mm² |
Cross section range AWG | (converted acc. to IEC) |
Hole diameter | 6.5 mm |
Width | 15 mm |
Bolt length | 22.5 mm |
Bolt diameter | 6 mm |
Screw thread | M6 |
Tightening torque | 3 ... 6 Nm |
Connection in acc. with standard | DIN 46235:1983-07 |
Cross section | 6 mm² ... 25 mm² |
Cross section range AWG | (converted acc. to IEC) |
Hole diameter | 6.4 mm |
Width | 14 mm |
Bolt length | 22.5 mm |
Bolt diameter | 6 mm |
Screw thread | M6 |
Tightening torque | 3 ... 6 Nm |
Connection in acc. with standard | DIN 46237:1970-07 |
Cross section | 2.5 mm² ... 6 mm² |
Cross section range AWG | (converted acc. to IEC) |
Hole diameter | 6.5 mm |
Width | 11 mm |
Bolt length | 22.5 mm |
Bolt diameter | 6 mm |
Screw thread | M6 |
Tightening torque | 3 ... 6 Nm |
Width | 16 mm |
End cover width | 2 mm |
Height | 64 mm |
Depth | 56.1 mm |
Depth on NS 35/7,5 | 56.8 mm |
Depth on NS 35/15 | 64.3 mm |
Bolt length | 22.5 mm |
Pitch | 18 mm |
Color | gray |
Flammability rating according to UL 94 | V0 |
Insulating material group | I |
Insulating material | PA |
Static insulating material application in cold | -60 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Surge voltage test | |
Test voltage setpoint | 9.8 kV |
Result | Test passed |
Short-time withstand current 35 mm² | 4.2 kA |
Result | Test passed |
Power-frequency withstand voltage | |
Test voltage setpoint | 2.2 kV |
Result | Test passed |
Mechanical data | |
Open side panel | No |
Mechanical strength | |
Result | Test passed |
Attachment on the carrier | |
DIN rail/fixing support | NS 35 |
Test force setpoint | 10 N |
Result | Test passed |
Needle-flame test | |
Time of exposure | 30 s |
Result | Test passed |
Oscillation/broadband noise | |
Specification | DIN EN 50155 (VDE 0115-200):2018-05 |
Spectrum | Service life test category 1, class B, body mounted |
Frequency | f1 = 5 Hz to f2 = 150 Hz |
ASD level | 0.964 (m/s²)²/Hz |
Acceleration | 5.72g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Result | Test passed |
Shocks | |
Pulse shape | Half-sine |
Acceleration | 5g |
Shock duration | 30 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Result | Test passed |
Ambient conditions | |
Ambient temperature (operation) | -60 °C ... 105 °C (max. short-term operating temperature RTI Elec.) |
Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Ambient temperature (assembly) | -5 °C ... 70 °C |
Ambient temperature (actuation) | -5 °C ... 70 °C |
Permissible humidity (storage/transport) | 30 % ... 70 % |
Connection in acc. with standard | IEC 60947-7-1 |
Mounting type | NS 35/7,5 |
NS 35/15 |