Product type | Current transformer |
Test voltage | 3 kV (EN 61869-1) |
Rated insulation voltage | 0.72 kV |
Measuring coil | |
Length of signal cable | 3 m |
General | |
Converter type | Split-core current transformer |
Current transformers | |
Rated power | 0.2 VA |
Thermal rated short-time current | Ith = 60 * In |
Thermal rated continuous current | Id = 1.2 * In |
Rated surge current | Idyn = 2.5 * Ith |
Rated frequency fn | 50 Hz |
60 Hz | |
Primary rated current range | 0 A AC ... 50 A AC (depends on type) |
Converter type | Split-core current transformer |
Signal | |
Designation | Current output |
Secondary rated current range Isn | 0 A AC ... 1 A AC |
Surge current limitation factor | FS 10 |
Accuracy class | 1 |
Secondary connection | |
Connection method | Single wires |
Width | 73 mm |
Height | 35 mm |
Depth | 22 mm |
Primary round conductor (diameter) | 13 mm |
Item dimensions | |
Width | 73 mm |
Height | 35 mm |
Depth | 22 mm |
Circular conductor | |
Diameter | 13 mm (Inner hole) |
Signal line | |
Length | 3 m |
Flammability rating according to UL 94 | V0 |
Housing material | PC |
Ambient conditions | |
Ambient temperature (operation) | -40 °C ... 65 °C |
Ambient temperature (storage/transport) | -45 °C ... 80 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | Use only indoors, non-condensing |
Standards/regulations | IEC 61010-1 |
IEC 61010-2-032 | |
IEC 61869-1 | |
IEC 61869-2 |