Количество
|
Стоимость
|
||
|
Input voltage | 24 V DC (SELV) |
Nominal capacity | 4 Ah |
Charging current | 1.2 A |
Output | |
Output voltage | 24 V DC |
Output current | max. 25 A |
Output fuse | 1x 25 A |
Buffer time | 4.5 min. (20 A) |
3 min. (25 A) | |
General | |
Connection in parallel | yes |
max. 5 | |
Connection in series | No |
Battery type | BB Battery HR4.2-12FR |
Battery technology | VRLA-AGM |
IQ-Technology | yes |
Latest startup date (battery only) | 6 Months (0 °C ... 20 °C) |
Latest startup (battery only) - range | 3 Months ... 6 Months (20 °C ... 30 °C) |
1 Months ... 3 Months (30 °C ... 40 °C) | |
Accumulator module service life (according to Eurobat) | 6 (20 °C) |
Storage medium | VRLA-AGM |
Size designation | Block |
Battery pack | yes |
Suitable for fast charging | yes |
Temperature sensor | yes |
Disposal | Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. |
Conductor connection | |
Connection method | Screw connection |
rigid | 4 mm² ... 6 mm² |
flexible | 4 mm² |
rigid (AWG) | 12 (Cu) |
Stripping length | 8 mm |
Tightening torque | 0.5 Nm ... 0.6 Nm |
5 lbf-in. ... 7 lbf-in. | |
Drive form screw head | Slotted L |
Product type | Battery unit |
Product family | Energy storage |
Application | for QUINT4 DC-UPS, QUINT4 AC-UPS, QUINT-UPS, and TRIO-UPS-2G |
Disposal | Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. |
Insulation characteristics | |
Protection class | III |
Degree of pollution | 2 |
Item dimensions | |
Width | 85 mm |
Height | 191 mm |
Depth | 110 mm |
Installation dimensions | |
Installation distance right/left | 0 mm / 0 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Housing material | Metal |
Type of housing | Galvanized sheet steel, powder-coated |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (storage/transport) | -20 °C ... 40 °C |
Ambient temperature (charge) | 0 °C ... 40 °C |
Ambient temperature (discharge) | -20 °C ... 50 °C |
Max. permissible relative humidity (operation) | ≤ 95 % |
Shock | 15g, 11 ms, in each space direction (in accordance with IEC 60068-2-27) |
Vibration (operation) | 5 Hz … 100 Hz, 0.7g (in accordance with DNV/IEC 600068-2-6) |
UL | |
Identification | UL/C-UL Listed UL 61010-1 |
UL | |
Identification | UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
Shipbuilding | |
Identification | DNV |
Shipbuilding | |
Identification | ABS |
Shipbuilding | |
Identification | LR |
Shipbuilding | |
Identification | BV |
Suited for EX-applications | No |